0,6/1kV YSLYCY-JZ/JB (Transparent)

Application

Power, control and connecting cable in electrical facilities for lossless data and signal transmission, fixed laying and flexible

applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms.

Outdoor use only with UV-protection, no laying underground.

Cable Structure & Features

Conductor material bare copper strand
Condustor type acc. To Din VDE 0295 resp, IEC 60228 class5
Core insulation PVC
Core identification
acc. To Din VDE 0293 black cores with white
numerals or colour coded with or without gn/ye
Stranding stranded in layers
Inner sheath material PVC Grey, RAL 7001
Overall shield copper braid tinned, coverage approx. 75%
Outer sheath  PVC
Sheath colour Transparent
Special Features / Remarks
  • 4kV testing voltage
  • largely resistant to acids, bases and usual oils
  • free from lacquer damaging substances and silicone (during production)
  • additional mechanical protection by inner sheath
  • recommended for EMC-application
  • confirm to RoHS
  • confirm to 73/23/EWG-Guideline CE
  • We are pleased to produce special versions, other dimensions, core and jacket colour on request.
Technical data
Standed acc. to DIN VDE 0245, 0250 and 0281
Rated Voltage Uo/U 600/1000V
Testing voltage 4kV
Conductor resistance acc. to DIN VDE 0295 class 5 resp. IEC 60228 class 5
Insulation resistance min. 20 M x km
Current carrying capacity acc. to DIN VDE, see Tecnical Guideline
Min. bending radius fixed 6 x d
Min. bending radius moved 15 x d
Operating temp. Fixed min/max -30ºC / +80ºC
Operating temp. moved min/max -5ºC / +80ºC
Condustor temp.
+70 °C in operation; +150°C in case of short-circuit
Burning behavior
self-extinguishing and flame-retardant acc.
to IEC 60332-1