DRAKA MAX-FOH (I) SINGLE INSULATION SINGLE CORE FIRE RESISTANT CABLE
DRAKA MAX-FOH (i) Single Insulation Single Core Fire Resistant Cable
CU/MGT/XLEVA 600/1000V TO IEC 60332-3-22, IEC 60331-21, SS299/BS6387 CAT.CWZ
Application
For use in most power and control circuits.Halogen-free replacement for PVC insulation to reduce hazardous gas emission and secondary damage. Suitable for fire alarm, lighting system due to small overall diameter.
Cable Structure & Features
Conductor material | (CU) Plain annealed stranded circular copper conductor, Class 2 |
Fire proof layer | (MGT) Mica tape to IEC60331-21/SS229-1/BS6387 |
Insulation | (XLEVA) XLEVA compound |
Applicable standards | |
Design standard: Conductor standarf: Flame propagation: Fire integrity: Corrosive gas emission: Smoke emission: Halogen-free: |
IEC 60502-1 IEC 60228, BS 6360 IEC 60332-3-22 IEC 60331-21, SS299-1/BS6387 Cat. CWZ IEC 60754-2 IEC 61034-2 IEC 60754-1 |
Technical Data
Sheath colour | Black or Red (Other sheath colours are available) |
Printing | Yes |
Rated voltage | 600/1000V |
Min. insulation Resistance @ 20ºC | 2000MΩ/km |
Test voltage | 3.5KV/5 min |
Short circuit temperature | 250°C |
Max. conductor temperature | 90°C |
Operating temperature range | -15°C / +110°C |
Installation temperature | 0°C / +50°C |
Minimum bending radius | 6 x overall diameter |