FABER KABEL Armoured Silicone Insulated Cable SiHF/GLS-P

Application

For connection of electrical appliances with high mechanical stress at increased environmental temperatures,
for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils,
acids, lyes and oxydants.
Construction and technical data
Conductor material tinned copper
Conductor construction fine stranded, class 5
Insulation: silicone rubber
Covering braided glass fibers
Armour round or flat steel wires, galvanized
Sheathing material: silicone rubber
Flame-retardant: VDE 0482-332-1-2 / IEC 60332-1-2
Oil resistant yes
Radiation resistance 20 x 10exp6 cJ/kg
Maximum temperature at conductor, °C: 180 °C
Maximum operating temperature, fixed, °C: -60 – +180 °C
Bending radius, fixed installation: 10 x DA
Insulation resistance: 2000 Ω x km
Nominal voltage Uo/U 300/500V
Test voltage: 2kV
Core identification: colours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Short circuit current (1s) 10.01 kA