Draka ALUPAC Instrumentation cable (Hydrocarbon Resistance Cable)
Draka ALUPAC Instrumentation cable (Hydrocarbon Resistance Cable)
CU/XLPE/OSCR/ALUPAC/SWA/LSHF-AT-AR 500V TO IEC60332-3-22
CU/XLPE/ISOS/ALUPAC/SWA/LSHF-AT-AR 500V TO IEC60332-3-22
Application
Multipair instrumentation cable for interconnection of measuring devices e.g. pressure and temperature gauges, flow meters, process-control systems, etc. Cable suitable for permanent installation in an agressive chemical environment. Not suitable for power installations and direct connection to the main power supply.
Construction
Conductor: | (Cu) Plain annealed stranded copper conductor Class 2, IEC 60228, BS6360 |
Insulation : | (XLPE) Cross-linked Polyethylene compound |
Pairing / Twining | Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping |
Assembly: | Multiple pairs/triads/quads are cabled together, supplied with non-hygroscopic filler (optional) to obtain a circular construction and covered with a polyester tape wrapping |
Overall screen: | (OSCR) Min. 30% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Moisture Barrier EMI protection: (ALUPAC) | Min. 30% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Inner Covering: (ALUPAC) |
the cable assembly is completely covered with an aluminium foil, coated on one side.
|
Inner covering: (ALUPAC) | Polyamide Nylon-12 compound. Black |
Armour: | galvanised steel wire armour. |
Outer Sheath | (LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives. Black (Optional: Blue colour for Intrinsically Safe) |
Insulation color | 1 pair in Black & White 2 pair & above -each pair in Black & White core with numbering. 1 triad in Black, White & Red 2 triad & a bove –each triad in Black, White & Red printed with numbering. |
Technical Data
Reference Standard | BS EN 50288-7 |
Voltage | 500V |
Max Operating Temperature | +90ºC |
Halogen Free | IEC 60754 |
Low Smoke Emission | IEC 61034 |
Flame Retardant | IEC 60332-3-22 |
Max. Conductor Resistance | ≤7.41Ω/km at 20°C(2.5mm²) ≤12.1Ω/km at 20°C(1.5 mm²) |
Max. Mutual Capacitance(at 1 KHz) | ≤ 150pF/min (1.5-2.5 mm²) |
Max. L /R Ratio | ≤ 40μF/min (1.5-2.5 mm²) |
Test Voltag | 2000Vac for 1 minute |
Bending Radius | 10 x overall diameter |